User`s manual
INP-TN5A0202-E 5-57
5.6 Setting/Monitor Area Entry Numbers (Control module)
Contents
Reading out/Writing
data setting range
Depends
on Input
range
Factory-set
value
Register
No.1
(Ch1)
Register
No.2
(Ch2)
Register
No.3
(Ch3)
Register
No.4
(Ch4)
Entry
ban
DO3 option function setting 0000 to 1111
bit0: Alarm latch
function
bit1: Error input alarm
function
bit2: Non-excitation
output function
bit3: Hold reset
function
0000 41052 42052 43052 44052
DO4 output event type setting 0 to 102 0 41056 42056 43056 44056
*
DO4 option function setting 0000 to 1111
bit0: Alarm latch
function
bit1: Error input alarm
function
bit2: Non-excitation
output function
bit3: Hold reset
function
0000 41060 42060 43060 44060
DO5 output event type setting 0 to 102 0 41064 42064 43064 44064
*
DO5 option function setting 0000 to 1111
bit0: Alarm latch
function
bit1: Error input alarm
function
bit2: Non-excitation
output function
bit3: Hold reset
function
0000 41068 42068 43068 44068
Ramp SV ON/OFF 0: OFF
1: ON
1 (ON) 41299 42299 43299 44299
Ramp SV-decline 0 to 100% FS
c
0 41300 42300 43300 44300
Ramp SV-incline 0 to 100% FS
c
0 41301 42301 43301 44301
Ramp SV slope time units 0: Slope deg/hr.
1: Slope deg/min.
0 (Slope deg/
hr.)
41302 42302 43302 44302
Control method 0: PID
1: FUSSY PID
2: PID against
open-loop
0 (PID) 41291 42291 43291 44291
ON/OFF hysteresis setting 0: OFF
1: ON
1 (ON) 41292 42292 43292 44292
Mode at startup 0: Auto
1: Manual
2: Remote
3: Standby
0 (Auto) 41304 42304 43304 44304
*