User`s manual

INP-TN5A0202-E 5-55
5.6 Setting/Monitor Area Entry Numbers (Control module)
Contents
Reading out/Writing
data setting range
Depends
on Input
range
Factory-set
value
Register
No.1
(Ch1)
Register
No.2
(Ch2)
Register
No.3
(Ch3)
Register
No.4
(Ch4)
Entry
ban
DI-1 function select 0: No function
1: RUN
/Standby switch
2: Auto/Manual switch
3: Local
/Remote switch
4: No function
5: No function
6: Start AT
(Normal type)
7: Start AT
(Low voltage PV)
8: No function
9: No function
10: Ramp SV ON/OFF
11: Ramp SV Hold
12: No function
13: No function
14: No function
15: No function
16: No function
17: Unlatch (All)
18: Unlatch (DO1)
19: Unlatch (DO2)
20: Unlatch (DO3)
21: Unlatch (DO4)
22: Unlatch (DO5)
23: No function
24: No function
25: No function
26: Start timer (DO1)
27: Start timer (DO2)
28: Start timer (DO3)
29: Start timer (DO4)
30: Start timer (DO5)
31: No function
32: No function
33: No function
34: No function
35: No function
0 41013 42013 43013 44013