5.6 Setting/Monitor Area Entry Numbers (Control module)
Setup Parameters
Contents
Reading out/Writing
data setting range
Depends
on Input
range
Factory-set
value
Register
No.1
(Ch1)
Register
No.2
(Ch2)
Register
No.3
(Ch3)
Register
No.4
(Ch4)
Entry
ban
PV input type 0: JPt100
(0 to 150°C)
1: JPt100
(-150 to 600°C)
2: Pt100
(0 to 150°C)
3: Pt100
(-150 to 300°C)
4: Pt100
(-150 to 850°C)
5: J (0 to 400°C)
6: J (0 to 800°C)
7: K (0 to 400°C)
8: K (0 to 800°C)
9: K (0 to 1200°C)
10: R
(0 to 1600°C)
11: B
(0 to 1800°C)
12: S
(0 to 1600°C)
13: T
(-199 to 400°C)
14: E
(-199 to 800°C)
18: N
(0 to 1300°C)
19: PL-2
(0 to 1300°C)
21: Voltage (0 to 5V)
22: Voltage (1 to 5V)
23: Voltage (0 to 10V)
24: Voltage (2 to 10V)
7(TC/Pt)
22(VI)
40151
41029
40152
42029
40153
43029
40154
44029
*
PV input scale lower -1999 to 9999 0% FS 41212 42212 43212 44212
*
PV input scale upper -1999 to 9999 100% FS 41213 42213 43213 44213
*
Decimal place 0: No decimal point
1: One decimal place
2: Two decimal places
0 41214 42214 43214 44214
*
Temperature unit 0: °C
1: Not selectable
°C 41215 42215 43215 44215
*
PV input shift -10 to 10% FS
c
0 41216 42216 43216 44216
SV set value shift -50 to 50% FS
c
0 41217 42217 43217 44217
PV input fi lter 0.0 to 120.0sec 2.0 41220 42220 43220 44220
PV display zero adjustment -50 to 50% FS
c
0 41221 42221 43221 44221
PV display span adjustment -50 to 50% FS
c
0 41222 42222 43222 44222
Cold junction compensation 0: OFF
1: ON
1 (ON) 41223 42223 43223 44223
RSV zero adjustment -50 to 50% FS
c
0 41225 42225 43225 44225
RSV span adjustment -50 to 50% FS
c
0 41226 42226 43226 44226
Remote input master St.
No.
0 to 255 0 41532 42532 43532 44532
*