5.6 Setting/Monitor Area Entry Numbers (Control module)
Control (PID) Parameters
Contents
Reading out/Writing data
setting range
Depends
on Input
range
Factory-
set value
Register
No.1
(Ch1)
Register
No.2
(Ch2)
Register
No.3
(Ch3)
Register
No.4
(Ch4)
Entry
ban
Proportional band [P] 0.0 to 999.9% 5.0 41102 42102 43102 44102
Integration time [I] 0 to 3200sec 240 41103 42103 43103 44103
Derivation time [D] 0.0 to 999.9sec 60.0 41104 42104 43104 44104
ON/OFF control hysteresis 0 to 50% FS
c
0.25% FS 41105 42105 43105 44105
Cooling proportional band coeffi cient [cool]
0.0 to 100.0 1.0 41106 42106 43106 44106
Dead band -50.0 to 50.0% 0 41107 42107 43107 44107
Output convergence value -100.0 to 100.0% 0 41108 42108 43108 44108
Anti-reset windup [ARW] 0 to 100% FS
c
100% FS 41109 42109 43109 44109
Direct/Reverse action setting
[MV1/MV2]
0: Reverse/None
1: Direct/None
2: Reverse/Direct
3: Direct/Reverse
4: Reverse/Reverse
5: Direct/Direct
0 41110 42110 43110 44110
SV Lower Limit 0 to 100% FS
c
0% FS 41218 42218 43218 44218
SV Upper Limit 0 to 100% FS
c
100% FS 41219 42219 43219 44219
MV1 Lower Limit -3.0 to 103.0% -3.0 41255 42255 43255 44255
MV1 Upper Limit -3.0 to 103.0% 103.0 41256 42256 43256 44256
MV2 Lower Limit -3.0 to 103.0% -3.0 41257 42257 43257 44257
MV2 Upper Limit -3.0 to 103.0% 103.0 41258 42258 43258 44258
Output limiter type setting 0: MV1 -3.0%/103.0%
MV2 -3.0%/103.0%
1: MV1 Limit/103.0%
MV2 -3.0%/103.0%
2: MV1 -3.0%/Limit
MV2 -3.0%/103.0%
3: MV1 Limit/ Limit
MV2 -3.0%/103.0%
4: MV1 -3.0%/103.0%
MV2 Limit/103.0%
5: MV1 Limit/103.0%
MV2 Limit/103.0%
6: MV1 -3.0%/Limit
MV2 Limit/103.0%
7: MV1 Limit/Limit
MV2 Limit/103.0%
8: MV1 -3.0%/103.0%
MV2 -3.0%/Limit
9: MV1 Limit/103.0%
MV2 -3.0%/Limit
10: MV1 -3.0%/Limit
MV2 -3.0%/Limit
11: MV1 Limit/Limit
MV2 -3.0%/Limit
12: MV1 -3.0%/103.0%
MV2 Limit/Limit
13: MV1 Limit/103.0%
MV2 Limit/Limit
14: MV1 -3.0%/Limit
MV2 Limit/Limit
15: MV1 Limit/Limit
MV2 Limit/Limit
0 41259 42259 43259 44259