User`s manual

INP-TN5A0202-E 5-51
5.6 Setting/Monitor Area Entry Numbers (Control module)
5.6
Setting/Monitor Area Entry
Numbers (Control module)
The table below shows the register numbers of a control module, which are settable to each parameter of "Setting/Monitor area
entry St. No." and "Setting/Monitor area entry register No." of a programless communication module.
Note
Parameters marked "*" in the "Entry ban" column in the table can not be changed via programless communication modules.
Do not set them to each parameter of "Setting/Monitor area entry St. No." and "Setting/Monitor area entry register No."
Operation parameter
Contents
Reading out/Writing data
setting range
Depends
on Input
range
Factory-set
value
Register
No.1
(Ch1)
Register
No.2
(Ch2)
Register
No.3
(Ch3)
Register
No.4
(Ch4)
Entry
ban
Local SV value 0 to 100% FS
c
0 40001
41001
40002
42001
40003
43001
40004
44001
*
Communication SV value 0 to 100% FS
c
0 40023
41100
40024
42100
40025
43100
40026
44100
MV value -3.0 to 103.0% - 40005
41002
40006
42002
40007
43002
40008
44002
Manual mode switch 0: Auto
1: Manual
0 (Auto) 40013
41003
40014
42003
40015
43003
40016
44003
RUN/Standby switch 0: RUN
1: Standby
0 (RUN) 40017
41004
40018
42004
40019
43004
40020
44004
Remote mode switch 0: Local
1: Remote
0 (Local) 40009
41007
40010
42007
40011
43007
40012
44007
Auto-tuning RUN
command
0: Stop/End
1: Normal type
2: Low PV type
0 41005 42005 43005 44005
DO output
unlatch command
0: OFF
1: Unlatch
0 41031 42031 43031 44031
ALM1 set value 1 -100 to 100% FS
c
2.5% FS 41033 42033 43033 44033
ALM1 set value 2 -100 to 100% FS
c
2.5% FS 41034 42034 43034 44034
ALM2 set value 1 -100 to 100% FS
c
2.5% FS 41041 42041 43041 44041
ALM2 set value 2 -100 to 100% FS
c
2.5% FS 41042 42042 43042 44042
ALM3 set value 1 -100 to 100% FS
c
2.5% FS 41049 42049 43049 44049
ALM3 set value 2 -100 to 100% FS
c
2.5% FS 41050 42050 43050 44050
ALM4 set value 1 -100 to 100% FS
c
2.5% FS 41057 42057 43057 44057
ALM4 set value 2 -100 to 100% FS
c
2.5% FS 41058 42058 43058 44058
ALM5 set value 1 -100 to 100% FS
c
2.5% FS 41065 42065 43065 44065
ALM5 set value 2 -100 to 100% FS
c
2.5% FS 41066 42066 43066 44066