User`s manual
5-22 INP-TN5A0202-E
5.5 Address Map and Data Format
PLC communication setting
Contents Reading out/Writing data setting range
Factory-set
value
Register No.
PLC communication speed 0005h: 9600bps
0007h: 19200bps
0009h: 38400bps
000Ah: 57600bps
000Bh: 115200bps
000Ch: 230400bps
000Bh 40001
PLC transmission setting b0: OFF (fi xed)
b1: Data bit (ON: 8bits (fi xed))
b2: Parity bit (OFF: No, ON: Yes)
b3: Odd/Even parity (OFF: Odd ON: Even)
b4: Stop bit (OFF: 1, ON: 2)
b5 to b15: OFF (fi xed)
000Eh 40002
MC protocol 2: Type 2
4: Type 4
5: Type 5
5 40003
PLC communication inter-cycle
time
0 to 5000ms 100 40004
PLC communication starting time 1 to 255sec 1 40005
PLC response monitoring time 10 to 10000ms 200 40006
Number of retry times 0 to 10 times 0 40007
Programless communication module operation setting
Contents Reading out/Writing data setting range
Factory-set
value
Register No.
Operation selection at
programless communication fault
0000h: RUN
0001h: STOP
0001h 40010