3 PLC Communication
© Copyright Reserved Autonics Co., Ltd. 73
3.3.2.2 GP, LP configuration
(1) Mono type
Before downloading drawn data from GP Editor: Synchronize communication configurations
of between GP/LP and GP Editor.
After downloading drawn data from GP Editor: After downloading PLC protocol (CT6M-2P)
of CH2, it starts communication between the specified PLC and GP/LP through
communication configuration.
1st Enter system setting menu.
Touch left-upper point as default position of system setting menu.
2nd Select [SET ENVIRONMENT]-[PLC SETTING].
3rd CH2 protocol is set as CT6M-2P as PLC type from GP Editor but downloaded CT6M-
2P protocol is not applied directly. (Communicates with EDITOR from CH2). Touch
protocol display item of CH2 to set CT6M-2P.
4th To communicate between GP/LP and CT6M-2P for CH2, desigante the connect port
for the specific PLC and use the dedicated cable. (Refer to ‘4 Communication Cable
By Device’.)
In case of CT6M-2P, it uses Modbus RS485(RS422) port. Set connect port item of
CH2 as RS422. Connect port display rotates in order as RS422RS232C with
touching.