3 PLC Communication
© Copyright Reserved Autonics Co., Ltd. 53
4th After downloading CH1 protocol is set as downloaded protocol ‘LS MASTER K200’
and CH2 protocol is set as ‘EDITOR’.
Touch protocol display item of CH2 to set as downloaded protocol ‘AUTONICS
CT6M-2P’.
5th To communicate between GP/LP and LS Master-K200 for CH1, desigante the
connect port for the specific PLC and use the dedicated cable. (Refer to ‘4
Communication Cable By Device’)
In case of LS Master-K200, it uses CPU module RS232C port. Set connect port item
of CH1 as ‘RS232C’. Connect port display rotates in order as RS422↔RS232C with
touching.
6th Synchronize the station of between GP/LP and LS Master-K200. Touch CH1 station
item and input key pad appears. Enter the same station of LS Master-K200.
7th Synchronize communicate specifications (baudrate, data bit, stop bit, parity, flow
control) of between GP/LP and LS Master-K200. The communicate specification of
downloaded PLC to GP/LP is set as default of the connected PLC and
communication is available directly. (Only when the communicate specification of
connected PLC is set as default)
Touch ‘CH1’ and detailed configuration screen is switched. Designate detailed
configuration.