User manual

6 Connectable PLC
268 © Copyright Reserved Autonics Co., Ltd.
6.16.2 Available device
UB device is as GP/LP inner bit memory, only in GP/LP it is able to use same as general inner
device of PLC.
It is able to switch into word UW device binding 16 units. However it is related with functional
area and it may cause serious error. Be sure to use only within user area UW30 to UW2047
(when not using recipe, UW30 to UW6047).
For further information of GP/LP inner memory, refer to 3.6 System signal’.
Refer to below bit/word available device organization and use the device.
UB 00 0
Device name Word address Bit address
Type
Bit UB Decimal Hexadecimal
Word
DP Word address(Hexadecimal)
UW Word address(Decimal) None
6.16.2.1 DPU digital power thyristor unit
(1) Modbus (DPU_Mod)
Type Device Mark
Range
Start End
Bit GP/LP inner bit memory UB UB0 UB6047F
Word
Word device area DP DP30001 DP30005
Word device area DP DP30101 DP30125
Word device area DP DP40001 DP40043
GP/LP inner word memory UW UW0 UW6047
Device Description
Enable
read/write
DP30001 Output voltage Read
DP30002 Load current Read
DP30003 Electric power Read
DP30004 Load resistance Read
DP30005 Power frequency Read
DP30101 Product number H Read
DP30102 Product number L Read
DP30103 Hardware version Read
DP30104 Software version Read
DP30105 Model name1 Read
DP30106 Model name2 Read
DP30107 Model name3 Read
DP30108 Model name4 Read
DP30109 Model name5 Read
DP30110 Model name6 Read
DP30111 Model name7 Read