6.16 KONICS Product connection
GP/LP is able to communicate with KONICS digital power thyristor unit DPU series and recorder
KRN50.
6.16.1 System organization
KONICS DPU sereis executes RS485 commnication and it executes also RS232C
communication with RS232/422 converter.
Controller type
Communication
method
Communication type
DPU RS485 CPU direct(Loader)
KRN50 RS485 CPU direct(Loader)
Wire as below for communicating GP/LP and RS485.
The below table is for communication configuration of digital power thyristor unit DPU seires with
GP/LP.
No
Item
Description
Note
1
Communication
mode
Modbus RTU
2 Baudrate 38400 bps(Default value of DPU) Selectable
3 Data type
Data length 8bit Selectable
Parity EVEN Selectable
Stop bit 1bit Selectable