Transmission speed setting
Baudrate(bps)
Bit unit
Baudrate (bps)
Bit unit
B15 to B8 B15 to B8
50 0Fh 14400 06h
300 00h 19200 07h
600 01h 28800 08h
1200 02h 38400 09h
2400 03h 57600 0Ah
4800 04h 115200 0Bh
9600 05h 230400 0Ch
If two interfaces connect to correspondence device respectively, the sum of communication
speed for both interfaces should be set 115,200bps or less(For QJ71C24N(-R2/R4),
230,400bps or less).
If only one interface connects to correspondence device, the communication speed for this
interface can be set the maximum 115,200bps.(For QJ71C24N(-R2/R4), available to set
maximum 230400bps).
In this case, please set the communication speed for the other interface to 300bps.