User manual

1 Product Overview
22 © Copyright Reserved Autonics Co., Ltd.
(3) CH1/ CH2 details configuration
No
Function and operation
Designate the device to be connected for CH1, CH2.
CH1, CH2 protocol: Communication mode for set PLC by GP and GP Editor by
each port.
EDITOR: I/O mode for downloading user-designed or PLC programming data
from GP Editor or SmartStudio.
PRINTER: Print mode for printing alarm history of GP.
Refer to 3.5.3 PRINTER communication configuration.
BARCODE: Input mode for reading data from barcode.
Refer to 3.5.2 Barcode reader communication configuration ’.
UNIVERSAL: It is general-purpose communication. GP/LP support Modbus slave
communication.
MK-200S(CPU): Default protocol of GP/LP. It is available to communication with
LS MK-200S.
MONITOR: Available only in CH2. Monitoring mode for PLC which is connected
to GP/LP from PC directly. GP/LP is as transmitter by transmitting data from PC to
PLC and data from PLC to PC. In case of MITSUBISHI FX-series, editor mode is
available for monitoring.
NoUse: Displayed only not using appropriate CH.
Touch this, detailed configuration screen for designated operation mode appears.
to
Designate detailed configuration for designated operation mode.
Baudrate: Designate baud rate.
Supports 300/600/1200/2400/4800/9600/19200/38400/57600/115200bps
Data: Designate data bit. Supports 7 bit, or 8 bit.
Stop bit: Designate stop bit. Supports 1 bit, or 2 bit.
Parity: Designate parity type. Supports even, odd, or none parity.
Flow control: Designate data flow control. Supports XON/ XOFF, or DSR/DTR.