User manual
6 Connectable PLC
154 © Copyright Reserved Autonics Co., Ltd.
6.1.3.2 MP
Available device and displayed parameter of Autonics MP series are as following. Available
device is only for MP series.
Type Device Mark
Range
Start End
Bit
GP/LP inner bit memory
UB UB0 UB6047F
Word
Word device area (32bit)
MP MP0 MP11
GP/LP inner word memory
UW UW0 UW6047
Device
Code
Description
Enable read/write
MP0 P0
Present value Read
MP1 C0
Compare setting
value(HH)
Read/Write
MP2 C1
Compare setting
value(H)
Read/Write
MP3 C2
Compare setting
value(L)
Read/Write
MP4 C3
Compare setting
value(LL)
Read/Write
MP5 K0
Peak value (Max.) Read
MP6 K1
Peak value (Min.) Read
MP7 X0
Prescale value X.Ain Read/Write
MP8 X1
Prescale value X.Bin Read/Write
MP9 Y0
Prescale value Y. A i n Read/Write
MP10 Y1
Prescale value Y. B i n Read/Write
MP11 R0
Max./Min. value reset Write
In MP device, downloaded data type have to be set as 32 bit for numeral display/input, ASCII
display/input of GP Editor to get accurate parameter value and to read/write right.