5.5.5 Exception response
It transmits function code response after set the most upper bit of function code master
transmitted as 1.
In case of reading 5 data of input register UW0000 to UW0004 with station no.5.
Query
Station
Function
code
Start address
The number of
read register
CRC
0x05 0x04 0x00 0x00 0x00 0x05 0x31 0x8D
Item Description
Station
Slave station is 05, 05 = (Hex)0x05
Function code
04. It is not available code.
Start address upper byte
0000 is a real address for 30001.
Start address lower byte
The number of read register
upper byte
The number of read register
lower byte
CRC lower byte
CRC upper byte
Response
Station
Function
code
Error
code
CRC
0x05 0x84 0x01 0x83 0x06
Item Description
Station
Slave station is 05, 05 = (Hex)0x05
Function code
84. The top bit is 1 in function code 04 transmitted by master.
Error code
01. Operation function code error not supported to slave.
CRC lower byte
CRC upper byte