Item Description
Alternation data 4 upper byte Upper byte value of data to write in UW103
Alternation data 4 lower byte Lower byte value of data to write in UW103
Alternation data 5 upper byte Upper byte value of data to write in UW104
Alternation data 5 lower byte Lower byte value of data to write in UW104
CRC lower byte
CRC upper byte
Response
Statio
n
Function
code
Start address
The number
of register
CRC
0x05 0x10 0x00 0x64 0x00 0x05 0x40 0x51
Item Description
Station
Slave station is 05, 05 = (Hex)0x05
Function code
16. 16 = (Hex)0x10
Start address upper byte
Start address is UW100.
100 = upper (Hex)0x00 + lower (Hex)0x64
Start address lower byte
The number of register upper byte
The total number of data to write.
5 = upper (Hex)0x00 + lower (Hex)0x05
The number of register lower byte
CRC lower byte
CRC upper byte