User manual
5 Universal (General-purpose communication)
© Copyright Reserved Autonics Co., Ltd. 143
Response
Station
Function
code
The
number of
data byte
Data 1 Data 2 Data 3
0x1F 0x03 0x0A 0x00 0x0A 0x00 0x14 0x00 0x1E
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
Data 4 Data 5 CRC
0x00 0x00 0x00 0x32 0x8F 0xD6
⑩ ⑪ ⑫ ⑬ ⑭ ⑮
Item Description
①Station
Slave station
②Function code
03
③the number of data byte
The total number of byte of data area.
Total 5Word=10byte
④, ⑥Data1
Upper byte of UW0000
Lower byte of UW0000
⑥, ⑦Data2
Upper byte of UW0001
Lower byte of UW0001
⑧, ⑨Data3
Upper byte of UW0002
Lower byte of UW0002
⑩, ⑪Data4
Upper byte of UW0003
Lower byte of UW0003
⑫, ⑬Data5
Upper byte of UW0004
Lower byte of UW0004
⑭, ⑮CRC
Lower byte
Upper byte