User manual

5 Universal (General-purpose communication)
142 © Copyright Reserved Autonics Co., Ltd.
5.5.3 03(Read holding register)
It reads contents of successive holding register. There is no Broadcast(Station designation of
Slave as 0). Available address is 00000 to 06047, it accords slave UW0000 to UW6047 of
GP/LP.
In case of reading 5 register data from UW0000 to UW0004 of GP/LP with station no.31
GP/LP
Station
Data(DEC)
Data(HEX)
UW0000 10 H000A
UW0001 20 H0014
UW0002 30 H001E
UW0003 40 H0028
UW0004 50 H0032
Query
Station
Function
code
Start address
The number of read
register
CRC
0x1F 0x03 0x00 0x00 0x00 0x05 0xE6 0x71
Item
Description
Station
Slave station is 31, 31=(HEX)0X1F
Function code
03
Start address upper byte
It conforms 0000
Start address lower byte
the number of read register upper byte Total 5.5=upper(HEX)0X00+lower(HEX)0X05
the number of read register lower byte
CRC lower byte
CRC upper byte