5.5.2 15(Force Multiple Coils)
It writes contents of successive coil. When designating (Broadcast) slave station as 0, it writes in
same address of slave.
Available address is 000240 to 65535, it accords slave UB00150 to UB4094F of GP/LP.
In case of writing next data in UB1000 to UB1004 of GP with station no. 05
Station Data
UB1000 OFF(0)
UB1001 ON(1)
UB1002 OFF(0)
UB1003 ON(1)
UB1004 ON(1)
Query
Stati
on
Function
code
Start
address
The number
of register
The
number
of data
byte
Alterna
tion
data
CRC
0x05 0x0F
0x0
6
0x4
0
0x00 0x05 0x01 0x1A 0xEE 0xC7
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩
Item Description
①Station
Slave station is 05, 05 = (Hex)0x05
②Function code
15. 15 = (Hex)0x0F
③Start address upper byte
Start address is UB1000.
UB1000(1600)=Upper(Hex)0x06 + Lower(Hex)0x40
④Start address lower byte
⑤The number of register upper byte
Total number of data to write
5 = Upper(Hex)0x00 + Lower(Hex)0x05
⑥The number of register lower byte
⑦The number of data byte
Total number of byte on data area
Total number of data to write: 5.
It is 5bit, it displays as 1byte. 1 = (Hex)0x01
⑧Alternation data byte Data value to write on UB1000
⑱CRC lower byte -