User`s manual

3 - 15 3 - 15
MELSEC-A
3 SPECIFICATION
3.6.3 CH.
input range setting (Address RWwm+1, RWwm+2)
(1) Set the analog input range per channel.
(2) Operation is performed according to the setting made for the leading edges of the
initial data setting request flag (RY(n+1)9).
(3) The default is as follows.
AJ65VBTCU-68ADV: -10 to +10V
AJ65VBTCU-68ADI : 4 to 20mA
b15 b12 b11 b8 b7 b4 b3 b0to
CH.4
to
CH.3
to
CH.2
to
CH.1RWwm+1
b15 b12
b11 b8 b7 b4 b3 b0to
CH.8
to
CH.7
to
CH.6
to
CH.5RWwm+2
Input Range Set Value
-10 to +10V 0
H
0 to 5V 1
H
1 to 5V 2
H
User range setting 1 (-10 to +10V) 3
H
AJ65VBTCU-68ADV
User range setting 2 (0 to 5V) 4
H
4to 20mA 0
H
0 to 20mA 1
H
AJ65VBTCU-68ADI
User range setting (0 to 20mA) 2
H
POINT
If the set value is outside the setting range, error "20 " occurs, the "RUN" LED
flickers at intervals of 0.1s, and all channels do not make A/D conversion.
indicates the channel No. where the error occurred.