3 - 13 3 - 13
MELSEC-A
3 SPECIFICATION
3.6 Remote Register
The AJ65VBTCU-68ADV/ADI has a remote resister for data communication with the
master module. The remote register allocation and data structures are described.
3.6.1 Remote register allocation
The remote register allocation is shown in Table 3.6.
Table 3.6 Remote register allocation
Communication direction Address Description Default value Reference section
RWwm A/D conversion enable/prohibit specification 0 Section 3.6.2
RWwm+1 CH.1 to 4 input range setting 0
RWwm+2 CH.5 to 8 input range setting 0
Section 3.6.3
RWwm+3 Average processing specification 0 Section 3.6.4
RWwm+4 CH.1 average time, number of times setting 0
RWwm+5 CH.2 average time, number of times setting 0
RWwm+6 CH.3 average time, number of times setting 0
RWwm+7 CH.4 average time, number of times setting 0
RWwm+8 CH.5 average time, number of times setting 0
RWwm+9 CH.6 average time, number of times setting 0
RWwm+A CH.7 average time, number of times setting 0
Master Remote
RWwm+B CH.8 average time, number of times setting 0
Section 3.6.5
RWrn CH.1 digital output value 0
RWrn+1 CH.2 digital output value 0
RWrn+2 CH.3 digital output value 0
RWrn+3 CH.4 digital output value 0
RWrn+4 CH.5 digital output value 0
RWrn+5 CH.6 digital output value 0
RWrn+6 CH.7 digital output value 0
RWrn+7 CH.8 digital output value 0
Section 3.6.6
RWrn+8 Error code 0 Section 3.6.7
Remote
Master
RWrn+9
to
RWrn+B
Reserved 0 ——
m, n: Address allocated to the master module by the station number setting.
POINT
Do not read or write data from or to the reserved area of the remote register. If data
is read or written, we cannot guarantee the functions of the AJ65VBTCU-
68ADV/ADI.