User`s manual

3 - 10 3 - 10
MELSEC-A
3 SPECIFICATION
3.5 Remote I/O Signals
This section describes the assignment and functions of the remote I/O signals.
3.5.1 Remote I/O signal list
Remote inputs (RX) mean the input signals from the AJ65VBTCU-68ADV/ADI to the
master module, and remote outputs (RY) mean the output signals from the master
module to the AJ65VBTCU-68ADV/ADI.
In communications with the master station, the AJ65VBTCU-68ADV/ADI uses 32
points of the remote inputs (RX) and 32 points of the remote outputs (RY).
This module occupies three stations but do not use the latter 64 points.
Table 3.4 indicates the assignment and names of the remote I/O signals.
Table 3.4 Remote I/O Signals List
Signal direction: AJ65VBTCU-68ADV/ADI Master Module Signal direction: Master Module AJ65VBTCU-68ADV/ADI
Remote input (RX) Signal name Remote output (RY) Signal name
RXn0 CH.1 A/D conversion completion flag
RXn1 CH.2 A/D conversion completion flag
RXn2 CH.3 A/D conversion completion flag
RXn3 CH.4 A/D conversion completion flag
RXn4 CH.5 A/D conversion completion flag
RXn5 CH.6 A/D conversion completion flag
RXn6 CH.7 A/D conversion completion flag
RXn7 CH.8 A/D conversion completion flag
RXn8
to
RXnB
Reserved
RXnC
E
2
PROM write error flag
RXnD
to
RX(n+1)7
Reserved
RYn0
to
RY(n+1)7
Reserved
RX(n+1)8 Initial data processing request flag RY(n+1)8 Initial data processing completion flag
RX(n+1)9 Initial data setting completion flag RY(n+1)9 Initial data setting request flag
RX(n+1)A Error status flag RY(n+1)A Error reset request flag
RX(n+1)B Remote READY
RX(n+1)C
to
RX(n+1)F
Reserved
RY(n+1)8
to
RY(n+1)F
Reserved
POINT
The reserved devices given in Table 3.4 are used by the system and cannot be
used by the user.
If the user has used (turned on/off) any of them, we cannot guarantee the functions