Specifications
Table Of Contents
- Title
- Safety Information
- Symbols used in the manual
- Table of Contents
- 1 Introduction
- 2 Profibus DP
- 3 CC-Link
- 4 Ethernet
- A Appendix
- Index

Appendix Process Images
A - 14
MITSUBISHI ELECTRIC
Status byte S1
Fig. A-16: Status byte S1 of the STL-ENC
Bit Name Description
0
MapPZD
앫 Software version XXXX03XX: reserved / not used (0)
앫 Software version XXXX03XX: coding of process data (2 Bits), refer to table A-12
1
2StaN1
앫 Software version XXXX03XX: reserved / not used (0)
앫 Software version XXXX03XX: state of cam output 1
0 = cam output 1 reset
1 = cam output 1 set
3StaN2
앫 Software version XXXX03XX: reserved / not used (0)
앫 Software version XXXX03XX: state of cam output 2
0 = cam output 2 reset
1 = cam output 2 set
4N1
Cam window 1st bit
This bit is set, if:
bottom comparative value N1 counter reading top comparative value N1
5N2
Cam window 2nd bit
This bit is set, if:
bottom comparative value N2 counter reading top comparative value N2
Tab. A-14: Description of the status byte S1 of the STL-ENC
b7 b6 b5 b4 b3 b2 b1 b0
0/10/10/10/10/10/100Status byte S1
MapPZD
MapPZD
StaN1
StaN2
N1
N2
Reserved
Reserved