Specifications

Table Of Contents
Ethernet Configuration Example for MELSEC System Q
4 - 18
MITSUBISHI ELECTRIC
Output data
Please note that the data for the digital output module is appended after the data for the analog out-
put module.
If you want to output 10 V on channel 1 of the STL-DA4-V1, write 32760 (7FF8
H
) to D2000.
4.3.3 The Web-Based Management System (WBM)
An internal file system and an integrated Web server can be used for configuration and administration
of the system. Together, they are referred to as the Web-Based Management System (WBM).
The HTML pages saved internally provide you with information about the configuration and status of
the fieldbus node. In addition, you can also change the configuration of the device here.
You can also save HTML pages created yourself via the implemented file system.
To open the WBM, launch a Web browser (e.g., Microsoft Internet Explorer or Mozilla Firefox).
Enter the IP address of the fieldbus coupler/controller in the address bar (192.168.1.1 by default
or as previously configured).
Click Enter to confirm. The start page of WBM loads.
Select the link to the desired HTML page in the left navigation bar. A query dialog appears.
Enter your user name and password in the query dialog
(default: user = "admin", password = "user" or user = "guest", password = "guest").
The corresponding HTML page is loaded.
Make the desired settings.
Press SUBMIT to confirm your changes or press UNDO to discard the changes.
Restart the system to apply the settings.
Abb. 4-15: Output data to the MODBUS/TCP node
NOTE
Always restart after making changes to the configuration!
The system must always be restarted for the changed configuration settings to take effect.
Output data to STL-DA4-V1, channel 1
Output data to STL-DA4-V1, channel 2
Output data to STL-DA4-V1, channel 3
Output data to STL-DA4-V1, channel 4
Outputs to STL-DO4