CC-Link Configuration Example for MELSEC System Q
3 - 20
MITSUBISHI ELECTRIC
Set the STlite modules to occupy 1 station. This will result in the following number of occupied devices
in the PLC.
Combined with the head addresses for the remote devices entered in the master parameter, the proc-
ess image is as follows (refer to section 3.2.8 and the appendix, section A.1):
Abb. 3-18: Parameter for the CC-Link slave station
Type of data
Number of
devices
Remote input RX (Inputs from digital input module STL-DI8-V1)
Total 32 points
User area 16 points
Remote output RY (Outputs to digital output module STL-DO4)
Total 32 points
User area 16 points
Remote register
RWr (Input data from analog input module STL-AD2-V) 4 points
RWw (Output data to analog out module STL-DA4-V1) 4 points
Tab. 3-28: Number of remote devices for the CC-Link slave station
Type of data Devices Remark
Remote inputs
RX (Inputs from
digital input mod-
ule STL-DI8-V1)
User area X1000 to X100F
X1000 to X1007: X0 to X7 of STL-DI8-V1
X1008 to X100F: Not used
System area X1010 to X101F —
Remote output
RY (Outputs to dig-
ital output module
STL-DO4)
User area Y1000 to Y100F
Y1000 to Y1003: Y0 to Y3 of STL-DO4
X1004 to X100F: Not used
System area Y1010 to Y101F —
Remote register
RWr (Input data from analog input
module STL-AD2-V)
D1000 to D1003
D1000: Channel 1, D1001: Channel 2
D1002, D1003: Not used
RWw (Output data to analog out
module STL-DA4-V1
D2000 to D2003
D2000: Channel 1, D2001: Channel 2
D2002: Channel 3, D2003: Channel 4
Tab. 3-29: Remote devices of the CC-Link slave station