Configuration Example for MELSEC System Q CC-Link
Quick Start Guide for the MELSEC STlite Series 3 - 19
3.3.2 Settings for the Slave Station
Station Address
For this example, the station address of the STL-BT1 is set to "1" (switch x1 = 1, switch x10 = 0, please
refer to section 3.2.4).
Transmission Speed and Address Mode
The transmission speed and address mode selector switch of the STL-BT1 is set to "9". This will result
in a transmission speed of 10 Mbit/s and auto address mode (see section 3.2.5). The auto address
mode is needed since the slave station is later set to occupy 1 station.
3.3.3 Configuring the CC-Link Network
Start GX Works2. In the project navigator window, open the Parameter, double click on Network
parameter and then on CC-Link.
Enter the following parameters for the master station.
Click on Station Information. This will open the screen shown on the next page.
Fig. 3-17: CC-Link master parameter