Profibus DP Configuration Example for MELSEC System Q
2 - 20
MITSUBISHI ELECTRIC
For the process images of the individual STlite modules please refer to the appendix, section A.1. For
example, reading a value of 16384 (4000
H
) from D1001 means that a voltage of 5.00 V is applied to
channel 1 of the STL-AD2-V or, if you want to output 10 V on channel 1 of the STL-DA4-V1, write 32760
(7FF8
H
) to D2001.
Rearrangement of the Modules
Another option for this example to allocate 16 bit input and output data to a single data register is to
mount first the analog modules and afterwards the digital modules.
The device monitor for this configuration is shown on the next page.
Fig. 2-17: Optimised allocation of the input and output data
Fig. 2-18: Configuration with analog modules mounted first
Slot 1: STL-DI8-V1
Slot 6: STL-AD2-V (Channel 1)
Slot 6: STL-AD2-V (Channel 2)
Slot 3: STL-DO4
Slot 5: STL-DA4-V1 (Channel 1)
Slot 5: STL-DA4-V1 (Channel 2)
Slot 5: STL-DA4-V1 (Channel 3)
Slot 5: STL-DA4-V1 (Channel 4)
Not used
Slot 2: STL-DI8-V2 (Dummy)
Slot 4: STL-DO4 (Dummy)
Analog modules