Profibus DP Head Station STL-PB1 (Profibus DP)
2 - 8
MITSUBISHI ELECTRIC
Bus Terminator
Each end of the Profibus DP network must be terminated with resistors. Since the STL-PB1 is not
equipped with built-in terminating resistors, use a Profibus connector with a bus terminator if the
STL-PB1 is situated at the beginning or end of a network.
Fig. 2-9: Termination of the Profibus
VP (6)
RXD/TXD-P (3)
RXD/TXD-N (8)
390 2%
min 1/4 W
220 2%
min 1/4 W
390 2%
min 1/4 W
GND (5)