2.2.4 Setting the Station Address
The station address (decimal) is determined using two rotary switches on the STL-PB1.
The switch “x1 “ determines the units position of the address, the switch “x10 “ determines the decimal
positions of the address (for example “x1“: 2, “x10 “: 4 -> address = 2 + 10 x 4 = 42).
Valid station addresses are between 1 and 99. The head station also permits the station address 0.
The station address is taken over by the head station after switching on the device (initialization
phase). Adjustments of the switch have no effect during operation.
2.2.5 Pin Configuration of the Profibus DP Interface
Fig. 2-6: Rotary switches of the STL-PB1
Fig. 2-7: 9-pin D-SUB female connector for
connection to Profibus
DP
Pin of the
D-SUB connector
Signal Description
1—Not used
2—Not used
3 RXD/TXD-P Receive/transmit data (+)
4RTSReady to send
5 GND Supply ground (earth)
6 VP Voltage supply
7—Not used
8 RXD/TXD-N Receive/transmit data (–)
9—Not used
Tab. 2-2: Pin configuration of the Profibus DP interface of the STL-PB1