Specifications
II Parameters
CC-Link Parameters
II - 242
【#24023+40(n-1)】 SLn SB dev No. Special relay (SB) refresh device No.
Set the refresh device No. of the special relay (SB) to be automatically refreshed.
"n" represents the expansion slot No.(n=1 to 3)
(Note 1) When setting parameters in ALL.PRM with using the parameter input/output
function, input the device No. of decimal digit.
(Example) When setting "X400" for the remote input (RX) refresh device No., input as
follows; #24014+40(n-1): "X" #24015+40(n-1): "1024"
(Note 2) When the refresh device name has been set, the refresh device No. will be
"0".Confirm the refresh device No. after changing the refresh device name.
When specifying a bit device, set the address in increments of 16 points.
The operation will not be guaranteed unless the address is set in increments of 16 points.
(Example) 1F0
---Master station---
Set a value within the setting range.
---Local/standby master station---
Set a value within the setting range.
---Setting range---
M: 0 to 10239
L: 0 to 511
B: 0 to 1FFF
D: 0 to 2047
W: 0 to 1FFF
SB: 0 to 1FF
R: 8300 to 9799, 9800 to 9899
【#24024+40(n-1)】 SLn SW dev name Special relay (SW) refresh device name
Set the refresh device name of the special relay (SW) to be automatically refreshed.
"n" represents the expansion slot No.(n=1 to 3)
(Example) SW
Set "0" when no setting is required.
---Master station---
Set a value within the setting range.
---Local/standby master station---
Set a value within the setting range.
---Setting range---
0,M,L,B,D,W,R,SW
【#24025+40(n-1)】 SLn SW dev No. Special relay (SW) refresh device No.
Set the refresh device No. of the special relay (SW) to be automatically refreshed.
"n" represents the expansion slot No.(n=1 to 3)
(Note 1) When setting parameters in ALL.PRM with using the parameter input/output
function, input the device No. of decimal digit.
(Example) When setting "X400" for the remote input (RX) refresh device No., input as
follows;
#24014+40(n-1): "X"
#24015+40(n-1): "1024"
(Note 2) When the refresh device name has been set, the refresh device No. will be
"0".Confirm the refresh device No. after changing the refresh device name.
When specifying a bit device, set the address in increments of 16 points.
(Example) 1F0
---Master station---
Set a value within the setting range.
---Local/standby master station---
Set a value within the setting range.
---Setting range---
M: 0 to 10239
L: 0 to 511
B: 0 to 1FFF
D: 0 to 2047
W: 0 to 1FFF
SW: 0 to 1FF
R: 8300 to 9799, 9800 to 9899
【#24026+40(n-1)(PR)】 SLn Protocol Ver Protocol version
Select the CC-Link version mode that has been set to the slide switch SW1-2 on the CC-
Link unit (HN566/HN567).
"n" represents the expansion slot No.(n=1 to 3)
0: Ver.2
1: Ver.1
Ver.2 mode has been set to SW1-2 as default.
---Master station---
Set to "0" or "1".
---Local/standby master station---
Set to "0" or "1".