Specifications

II Parameters
CC-Link Parameters
II - 240
#24013+40(n-1) SLn delay time Delay time
Set the delay time.
"n" represents the expansion slot No.(n=1 to 3)
0: (Fixed value)
---Master station---
Set to "0" (fixed).
---Local/standby master station---
Set to "0".
#24014+40(n-1) SLn RX dev name Remote input (RX) refresh device name
Set the refresh device name of the remote input (RX) to be automatically refreshed.
(Example) X
"n" represents the expansion slot No.(n=1 to 3)
Set "0" when no setting is required.
---Master station---
Set a value within the setting range.
---Local/standby master station---
Set a value within the setting range.
---Setting range---
0,X,M,L,B,D,W,R
#24015+40(n-1) SLn RX dev No. Remote input (RX) refresh device No.
Set the refresh device No. of the remote input (RX) to be automatically refreshed.
"n" represents the expansion slot No.(n=1 to 3)
(Note 1) When setting parameters in ALL.PRM with using the parameter input/output
function, input the device No. of decimal digit.
(Example) When setting "X400" for the remote input (RX) refresh device No., input as
follows; #24014+40(n-1): "X"
#24015+40(n-1): "1024"
(Note 2) When the refresh device name has been set, the refresh device No. will be
"0".Confirm the refresh device No. after changing the refresh device name.
When specifying a bit device, set the address in increments of 16 points.
The operation will not be guaranteed unless the address is set in increments of 16 points.
(Example) 1000
---Master station---
Set a value within the setting range.
---Local/standby master station---
Set a value within the setting range.
---Setting range---
X: 0 to 5FF
M: 0 to 10239
L: 0 to 511
B: 0 to 1FFF
D: 0 to 2047
W: 0 to 1FFF
R: 8300 to 9799, 9800 to 9899
#24016+40(n-1)(PR) SLn RY dev name Remote output (RY) refresh device name
Set the refresh device name of the remote output (RY) to be automatically refreshed.
(Example) Y
"n" represents the expansion slot No.(n=1 to 3)
Set "0" when no setting is required.
---Master station---
Set a value within the setting range.
---Local/standby master station---
Set a value within the setting range.
---Setting range---
0,Y,M,L,B,D,W,R
#24017+40(n-1) SLn RY dev No. Remote output (RY) refresh device No.
Set the refresh device No. of the remote output (RY) to be automatically refreshed.
"n" represents the expansion slot No.(n=1 to 3)
(Note 1) When setting parameters in ALL.PRM with using the parameter input/output
function, input the device No. of decimal digit.
(Example) When setting "X400" for the remote input (RX) refresh device No., input as
follows; #24014+40(n-1): "X" #24015+40(n-1): "1024"
(Note 2) When the refresh device name has been set, the refresh device No. will be
"0".Confirm the refresh device No. after changing the refresh device name.
When specifying a bit device, set the address in increments of 16 points.
The operation will not be guaranteed unless the address is set in increments of 16 points.
(Example) 1000
---Master station---
Set a value within the setting range.
---Local/standby master station---
Set a value within the setting range.
---Setting range---
Y: 0 to 5FF
M: 0 to 10239
L: 0 to 511
B: 0 to 1FFF
D: 0 to 2047
W: 0 to 1FFF
R: 8300 to 9799, 9800 to 9899