Specifications

II Parameters
CC-Link Parameters
II - 239
#24006+40(n-1)(PR) SLn extended cyc Extended cyclic setting
Set the magnification for the extended cyclic operation of the local station whose type
corresponds to Ver.2.
"n" represents the expansion slot No.(n=1 to 3)
Set "1" for the local station whose type corresponds to Ver.1.
This function is out of specifications when the protocol version is Ver.1. The setting for the
local station is fixed to "1".
---Master station---
Set to "0".
---Local/standby master station---
Set to either of "1", "2", "4" or "8".
---Setting range---
0,1,2,4,8 (fold)
#24007+40(n-1) SLn conn modules Number of connected modules
Set the total number of remote stations, local stations, intelligent device stations, standby
master station and reserved stations connected to the master station.
"n" represents the expansion slot No.(n=1 to 3)
---Master station---
Set to either of "1" to "64".
---Local/standby master station---
Set to "0".
---Setting range---
0 to 64 (modules)
#24008+40(n-1) SLn num of retries Number of retries
Set the number of retries for when a communication error occurs.
"n" represents the expansion slot No.(n=1 to 3)
---Master station---
Set to either of "1" or "7".
---Local/standby master station---
Set to "0".
---Setting range---
0 to 7 (times)
#24009+40(n-1) SLn auto ret mdls Number of automatic return modules
Set the total number of remote stations, local stations, intelligent device stations and
standby master station that can be returned to system operation by a single link scan.
"n" represents the expansion slot No.(n=1 to 3)
(Note) Refer to "CC-Link System Master/Local Module User's Manual (SH(NA)-080394E-
E)" for the details of the functions.
---Master station---
Set to either of "1" or "10".
---Local/standby master station---
Set to "0".
---Setting range---
0 to 10 (modules)
#24010+40(n-1)(PR) SLn STBY master st Standby master station
Set the station No. of the standby master station.
"n" represents the expansion slot No.(n=1 to 3)
Set "0" when no standby master station is provided.
---Master station---
Set a value within the setting range.
---Local/standby master station---
Set "0" (fixed) for the local station.
Set "1" (fixed) for the standby station.
---Setting range---
0 to 64
#24011+40(n-1) SLn ope at NC down Operation at NC down
Set the data link status for when the master station failure occurs.
"n" represents the expansion slot No.(n=1 to 3)
0: Fixed to stop
(Note) Refer to "CC-Link System Master/Local Module User's Manual (SH(NA)-080394E-
E)" for the details of the functions.
---Master station---
Set to "0" (fixed).
---Local/standby master station---
Set to "0".
#24012+40(n-1) SLn scan mode Scan mode
Select whether to synchronize the link scan with one ladder scan.
"n" represents the expansion slot No.(n=1 to 3)
0: Fixed to synchronize
---Master station---
Set to "0" (fixed).
---Local/standby master station---
Set to "0".