Specifications
II Parameters
Position Switches
II - 214
【#7544】 PSW5 check Selection of area check method
When position switch area checking at high speed is selected, specify the mode of area
checking, i.e., whether to use the command type machine position or detector feedback
position, for each position switch point.
0: Use the command type machine position as the machine position for position switch
area checking.
1: Use the detector feedback position as the machine position for position switch area
checking.
(Note) This parameter is valid only when “1” set in "#7500 Pcheck".
【#7551】 PSW6 axis Axis name
Specify the name of the axis for which a position switch is provided.
---Setting range---
X, Y, Z, U, V, W, A, B, or C axis address
【#7552】 PSW6 dog1 Imaginary dog position 1
When the machine enters the range between imaginary dog positions 1 and 2, a signal is
output to the PLC.
1st part system device: X1D05
2nd part system device: X1D25
---Setting range---
-99999.999 to 99999.999 (mm)
【#7553】 PSW6 dog2 Imaginary dog position 2
When the machine enters the range between imaginary dog positions 1 and 2, a signal is
output to the PLC.
1st part system device: X1D05
2nd part system device: X1D25
---Setting range---
-99999.999 to 99999.999 (mm)
【#7554】 PSW6 check Selection of area check method
When position switch area checking at high speed is selected, specify the mode of area
checking, i.e., whether to use the command type machine position or detector feedback
position, for each position switch point.
0: Use the command type machine position as the machine position for position switch
area checking.
1: Use the detector feedback position as the machine position for position switch area
checking.
(Note) This parameter is valid only when “1” set in "#7500 Pcheck".
【#7561】 PSW7 axis Axis name
Specify the name of the axis for which a position switch is provided.
---Setting range---
X, Y, Z, U, V, W, A, B, or C axis address
【#7562】 PSW7 dog1 Imaginary dog position 1
When the machine enters the range between imaginary dog positions 1 and 2, a signal is
output to the PLC.
1st part system device: X1D06
2nd part system device: X1D26
---Setting range---
-99999.999 to 99999.999 (mm)
【#7563】 PSW7 dog2 Imaginary dog position 2
When the machine enters the range between imaginary dog positions 1 and 2, a signal is
output to the PLC.
1st part system device: X1D06
2nd part system device: X1D26
---Setting range---
-99999.999 to 99999.999 (mm)
【#7564】 PSW7 check Selection of area check method
When position switch area checking at high speed is selected, specify the mode of area
checking, i.e., whether to use the command type machine position or detector feedback
position, for each position switch point.
0: Use the command type machine position as the machine position for position switch
area checking.
1: Use the detector feedback position as the machine position for position switch area
checking.
(Note) This parameter is valid only when “1” set in "#7500 Pcheck".
【#7571】 PSW8 axis Axis name
Specify the name of the axis for which a position switch is provided.
---Setting range---
X, Y, Z, U, V, W, A, B, or C axis address