Specifications

II Parameters
PLC Constants
II - 202
#17000 - 17063 ST0 - ST63 PLC integrated timer <100ms INC.>
Set the time for the integrated timer used with the PLC program (ladder).
(Note1) This setting value is valid when bit selection parameter "#6449/bit0" is set to "0".
(Note2) Setting the timer setting value from the setting and display unit
The timer T setting value can be set with the following two methods.
- Method to validate the setting value (Kn) programmed with the sequence program
(fixed integrated timer)
- Method to validate the setting value set from the setting and display unit (variable
integrated timer)
(Note3) As described bellow, the setting method of timer ST and No. of points can be set
with the bit selection parameters (#6453/bit5 to bit7).
- #6453/bit5=0, bit6=0, bit7=0
No. of points: 0
Range: None
Setting method: All fixed integrated timers
- #6453/bit5=1, bit6=0, bit7=0
No. of points: 20
Range: #17000 to #17019
Setting method: Set above range with variable integrated timer.
- #6453/bit5=0, bit6=1, bit7=0
No. of points: 40
Range: #17000 to #17039
Setting method: Set above range with variable integrated timer.
- #6453/bit5=1, bit6=1, bit7=0
No. of points: All points
Range: #17000 to #17063
Setting method: All variable integrated timers
---Setting range---
0 to 32767( x 100ms)
#17200 - 17455 C000 - C255 Counter
Set the time for the counter used with the PLC program (ladder).
(Note1) This setting value is valid when bit selection parameter "#6449/bit1" is set to "0".
(Note2) Setting the counter setting value from the setting and display unit
The counter C setting value can be set with the following two methods.
- Method to validate the setting value (Kn) programmed with the sequence program
(fixed counter)
- Method to validate the setting value set from the setting and display unit (variable
counter)
(Note3) As described bellow, the setting method of counter C and No. of points can be set
with the bit selection parameters (#6454/bit4 to bit7).
- #6454/bit4=0, bit5=0, bit6=0, bit7=0
No. of points: 0
Range: None
Setting method: All fixed counters
- #6454/bit4=1, bit5=0, bit6=0, bit7=0
No. of points: 40
Range: #17200 to #17239
Setting method: Set above range with variable counter.
- #6454/bit4=0, bit5=1, bit6=0, bit7=0
No. of points: 80
Range: #17200 to #17279
Setting method: Set above range with variable counter.
- #6454/bit4=1, bit5=1, bit6=0, bit7=0
No. of points: 120
Range: #17200 to #17319
Setting method: Set above range with variable counter.
- #6454/bit4=0, bit5=0, bit6=1, bit7=0
No. of points: 160
Range: #17200 to #17359
Setting method: Set above range with variable counter.
- #6454/bit4=1, bit5=0, bit6=1, bit7=0
No. of points: 200
Range: #17200 to #17399
Setting method: Set above range with variable counter.
- #6454/bit4=0, bit5=1, bit6=1, bit7=0
No. of points: 240
Range: #17200 to #17439
Setting method: Set above range with variable counter.
- #6454/bit4=1, bit5=1, bit6=1, bit7=0
No. of points: All points
Range: #17200 to #17455
Setting method: All variable counters
---Setting range---
0 to 32767
#18001 - 18150 R7500,7501 - R7798,7799 PLC constant (Base area)
Set the value to be set in the data type R register used in the PLC program (ladder).
Even if the data is set in the R register that corresponds to the PLC side when this
parameter is displayed. The screen will not change.Enter a different screen once, and then
select this screen again.
---Setting range---
-99999999 to 99999999