Specifications

II Parameters
Spindle Parameters
II - 191
#13229 SP229 SFNC9 Spindle function 9
Select the spindle functions.
Functions are allocated to each bit.
Set this in hexadecimal format.
bit F : ssc SLS (Safely Limited Speed) function
0: Disable 1: Enable
bit E :
Not used. Set to "0".
bit D : rps Safely limited speed setting unit
0: Normal 1: 100°/min
bit C : sdt2 Specified speed output digital signal 2 output
0: Normal 1: Enable
bit B-9 :
Not used. Set to "0".
bit 8 : sto Dedicated wiring STO function
Set this parameter to use dedicated wiring STO function.
0: Dedicated wiring STO function unused 1: Dedicated wiring STO function used
bit 7-1 :
Not used. Set to "0".
bit 0 : omrffon OMR-FF control enabled
0: Disable  1: Enable
#13230 SP230 SFNC10 Spindle function 10
Select the spindle functions.
Functions are allocated to each bit.
Set this in hexadecimal format.
bit F-C :
Not used. Set to "0".
bit B : pfdsr
Set the spindle stop operation at a power failure when the deceleration and stop function at
power failure is enabled.
Normal (Coast to a stop at power failure) : 0
Deceleration and stop at power failure : 8
bit A-9 :
Not used. Set to "0".
bit 8 : nohis History of communication error alarm between NC and DRV(34,36,38,39)
For C70, set "1".
0: Enable 1: Disable
bit 7 : cse Spindle C axis command speed monitoring function
0: Normal setting (function disabled) 1: Function enabled
bit 6-0 :
Not used. Set to "0".
#13231 SP231
Not used. Set to "0000".
#13232 SP232
Not used. Set to "0000".
sdt2
rps
ssc
sto
omrffon
cse
nohis
pfdsr