Specifications

II Parameters
Servo Parameters
II - 152
#2334 SV134 RRn0 Distance-coded reference check / revolution counter
Set this parameter to operate distance-coded reference check when using distance-coded
reference scale.
During the distance-coded reference check initial setup (SV137:RAER=-1), set the following
items on the NC drive monitor screen after the distance-coded reference check initial setup
warning A3 turns OFF.
SV134=Rn, SV135=Pn, SV136=MPOS
When reference point is set, the warning A3 turns OFF.
To enable the distance-coded reference check function, SV081/bit3=1setting and a battery
option are needed.
Related parameters: SV081/bit3,7, SV130, SV131, SV134 to SV137
---Setting range---
-32768 to 32767
#2335 SV135 RPn0H Distance-coded reference check /position within one rotation High
Set this parameter to operate distance-coded reference check when using distance-coded
reference scale.
During the distance-coded reference check initial setup (SV137:RAER=-1), set the following
items on the NC drive monitor screen after the distance-coded reference check initial setup
warning A3 turns OFF.
SV134=Rn, SV135=Pn, SV136=MPOS
When reference point is set, the warning A3 turns OFF.
To enable the distance-coded reference check function, SV081/bit3=1setting and a battery
option are needed.
Related parameters: SV081/bit3,7, SV130, SV131, SV134 to SV137
---Setting range---
-32768 to 32767
#2336 SV136 RPn0L Distance-coded reference check / position within one rotation Low
Set this parameter to operate distance-coded reference check when using distance-coded
reference scale.
During the distance-coded reference check initial setup (SV137:RAER=-1), set the following
items on the NC drive monitor screen after the distance-coded reference check initial setup
warning A3 turns OFF.
SV134=Rn, SV135=Pn, SV136=MPOS
When reference point is set, the warning A3 turns OFF.
To enable the distance-coded reference check function, SV081/bit3=1setting and a battery
option are needed.
Related parameters: SV081/bit3,7, SV130, SV131, SV134 to SV137
---Setting range---
-32768 to 32767
#2337 SV137 RAER Distance-coded reference check allowable width
For the distance-coded reference check function when using distance-coded reference
scale, set the allowable gap from the reference point position data calculated by the main
side detector. When the gap exceeds the allowable range, reference point created by
distance-code is judged as wrong and detects alarm 42.
The standard setting value is "basic reference mark interval (SV130) / 4".
SV137=0 setting carries out the same operation as the standard setting value.
SV137=-1 setting enables the distance-coded reference initial set up mode and displays
setting values of SV134 to SV136 on NC drive monitor.
To enable the distance-coded reference check function, SV081/bit3=1setting and a battery
option are needed.
When SV137=32767, the distance-coded reference check function is disabled.
Related parameters: SV081/bit3,7, SV130, SV131, SV134 to SV136
---Setting range---
-1 to 32767 (mm)
#2338-2397 SV138 - SV197
Not used. Set to "0".
#2398 SV198 NSE No signal 2 special detection width
Set the special detection width for the no signal 2 (alarm 21).
This detects no signal 2 (alarm 21) when machine side feedback is not invoked even if the
motor side detector feedback exceeds this setting in the rectangular wave signal output
linear scale.
When "0" is set, the detection will be performed with a 15μm width.
---Setting range---
0 to 32767 (μm)
#2399-2437 SV199 - SV237
Not used. Set to "0".