Specifications
II Parameters
Base Specifications Parameters
II - 90
【#1342】 AlmDly Alarm display delay time
Set a time between when an operation alarm occurs and when the alarm display and signal
turn ON.
When set to "0", the alarm display and signal will turn ON immediately after the alarm
occurrence.
When set to "-1", the alarm display and signal will not turn ON after the alarm
occurrence.
Target alarms:
M01 External interlock axis found 0004
M01 Internal interlock axis found 0005
M01 Sensor signal illegal ON 0019
M01 No operation mode 0101
---Setting range---
-1 to 30000 (ms)
【#1349(PR)】 DOOR_1 Door 1 switch input device
Set a remote I/O device to input the door sensor signal to detect Door 1's status in safety
observation.
When "0" is set, the door is always detected to be open.
Thus, "X0" cannot be used as Door 1 switch input device.
---Setting range---
0000 to 02FF (HEX)
【#1350(PR)】 DOOR_2 Door 2 switch input device
Set a remote I/O device to input the door sensor signal to detect Door 2's status in safety
observation.
When "0" is set, the door is always detected to be open.
Thus, "X0" cannot be used as Door 2 switch input device.
---Setting range---
0000 to 02FF (HEX)
【#1353(PR)】 MC_ct1 Contactor shutoff output 1 device
Set a device of an output remote I/O device to control contactor in safety observation.
When set to "0", contactor shutoff output is disabled.
Thus, "Y0" cannot be used as contactor shutoff output device.
---Setting range---
0000 to 02FF (HEX)
【#1357(PR)】 mchkt1 Contactor operation check allowed time 1
Set a period of time until emergency stop is issued when a contactor does not operate even
though contactor shutoff output 1 is output.
If the vertical axis drop prevention function is used, set a value bigger than the vertical axis
drop prevention time (SV048 EMGrt).
When "0" is set, the contactor operation check will be disabled.
---Setting range---
0 to 30000 (ms)
【#1361(PR)】 aux_acc Auxiliary axis acceleration/deceleration type
Select the acceleration/deceleration type of auxiliary axis in PLC axis indexing.
0: Acceleration/deceleration with constant time
1: Acceleration/deceleration with a constant angle of inclination
【#1365】 manualFtype Manual speed command type
Select the manual speed command type.
0: Manual speed command
The axis travels at the handle/jog feed rate.
Reverse run is performed for each part system independently of the other ones.
1: Manual speed command 2
In a multi-part system configuration, the axis travels at the handle/jog feed rate
multiplied by the ratio of each part system's program command speeds.
When the block start point is reached in reverse run in any of the part systems, the
axes in the other part systems stop simultaneously.
【#1366】 skipExTyp Multi-system simultaneous skip command
Select the operation when G31 is commanded in more than one part system.
(Note) When set to "1", the skip coordinate position will always be "0" whether G31 is
commanded in a single part system or in one part system of a multi-part system.
Set to "0" when using G31 command for measurement etc.
0: Carry out G31 command in one part system, while the G31 is kept in an interlocked
state in the other systems.
1: Carry out G31 command simultaneously in more than one part system.
Note that the skip coordinate is not read and so the skip coordinate value will be 0.
【#1367】 G1AccOVRMax Max. override value for cutting feed constant inclination acc./dec.
Set the maximum override value to be applied to the cutting feed that is in constant
inclination acceleration/deceleration.
When the setting of this parameter is between 0 and 99, the override value is handled as
100% even though the specified cutting feed override is over 100%.
---Setting range---
0 to 300(%)