Specifications

II Parameters
User Parameters
II - 31
#9306 DEV2 CHR. LENGTH
Select the length of the data bit.
Refer to "#9304 DEV2 PARITY CHECK".
0: 5 (bit)
1: 6
2: 7 (NC connection not supported)
3: 8
#9307 DEV2 TERMINATR TYP
Select the code to terminate data reading.
0, 3: EOR
1, 2: EOB or EOR
[When M700/700VW display side serial port is selected]
0: No terminator
1: EOR
2: EOB
3: EOB or EOR
#9308 DEV2 HAND SHAKE
Select the transmission control method.
No handshaking will be used when a value except 1 to 3 is set.
1: RTS/CTS method
2: No handshaking
3: DC code method
#9309 DEV2 DC CODE PRTY
Select the DC code type when the DC code method is selected.
0: Not add parity to DC code (DC3 = 13H)
1: Add parity to DC code (DC3 = 93H)
#9311 DEV2 DC2/4 OUTPUT
Select the DC code handling when outputting data to the output device.
DC2 / DC4
0: None / None
1: Yes / None
2: None / Yes
3: Yes / Yes
#9312 DEV2 CR OUTPUT
Select whether to add the (CR) code just before the EOB (L/F) code during output.
0: Not add
1: Add
#9313 DEV2 EIA OUTPUT
Select ISO or EIA code for data output.
In data input mode, the ISO and EIA codes are identified automatically.
0: ISO code output
1: EIA code output
#9314 DEV2 FEED CHR.
Set the length of the tape feed to be output at the start and end of the data during tape
output.
---Setting range---
0 to 999 (characters)
#9315 DEV2 PARITY V
Select whether to perform the parity check for the number of characters in a block at the
input of data.
At the output of data, the number of characters is always adjusted to for the parity check.
0: Not perform parity V check
1: Perform parity V check
#9316 DEV2 TIME-OUT (sec)
Set the time out time to detect an interruption in communication.
Time out check will not be executed when set to "0".
---Setting range---
0 to 30 (s)
#9317 DEV2 DR OFF
Select whether to enable the DR data check in data I/O mode.
0: Enable
1: Disable
#9318 DEV2 DATA ASCII
Select the code of the output data.
0: ISO/EIA code (Depends on whether #9113, #9213, #9313, #9413 or #9513 EIA
output parameter is set up.)
1: ASCII code
#9319 DEV2 INPUT TYPE
Select the mode for input (verification).
0: Standard input (Data from the very first EOB is handled as significant information.)
1: EOBs following the first EOB of the input data are skipped until data other than EOB
is input