Installation manual

[ II Restrictions ]
- 54 -
HWE10050 GB
2. Connecting the BC controller
(1) Size of the pipe that fits the standard BC controller ports
(E)P200 - (E)P350 models
* BC controllers can only be connected to (E)P200 - (E)P350 models of outdoor units.
Unit : mm [inch]
Operation
Pipe sections
High-pressure side (liquid) Low-pressure side (gas)
Outdoor unit side (E)P200 ø15.88 [5/8"] (Brazed connection) ø19.05 [3/4"] (Brazed connection)
(E)P250 ø19.05 [3/4"] (Brazed connection) ø22.2 [7/8"] (Brazed connection)
(E)P300 ø19.05 [3/4"] (Brazed connection) ø22.2 [7/8"] (Brazed connection)
(E)P350 ø19.05 [3/4"] (Brazed connection) ø28.58 [1-1/8"] (Brazed connection)
Indoor unit side ø9.52 [3/8"] (Flare connection) ø15.88 [5/8"] (Flare connection)
IndoorIndoorIndoor
Indoor
IndoorIndoor
BC controller
Maximum of 3 units per port
Total capacity of P80 or below
(All units connected to the same port
must be in the same operating mode.)
Branch joint (Model name:CMY-Y102S-G2)
(Optional accessory)
*2
Junction pipe kit
(Model name:
CMY-R160-J1)
(Optional accessory)
P50 model or below P63-P80 models P100-P250 models
3*
A
B
*1
Reducer
(Standard
supplied parts)
To outdoor unit
Connection: Brazed connection
The ports of the BC controller accommodates the pipes on P63-P140 models of indoor units.
To connect other types of indoor units, follow the procedure below.