Installation manual
[ II Restrictions ]
- 52 -
HWE10050 GB
7) The maximum capacity of the indoor units that is connectable to the CMB-P-V-GB1 types of sub BC controllers is P350 or
below (when two GB1 type controllers are connected P350 or below for both combined) .
The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016V-HB1 is P350 or below.
If at least one CMB-P1016V-HB1 unit is connected, the maximum total capacity of connectable indoor units to a system with
two sub controllers is P450 or below.
Restrictions on pipe length
[PURY-P200, 250, 300YJM-A, PURY-EP200YJM-A]
[PURY-P350, 400, 450YJM-A, PURY-EP250, 300, 350YJM-A]
[PURY-P400, 450YSJM-A1]
[PURY-P500, 550YSJM-A(1), PURY-EP400, 450, 500, 550YSJM-A(1)]
[PURY-P600, 650YSJM-A(1), PURY-EP600, 650, 700YSJM-A(1)]
[PURY-P700, 750, 800, 850, 900YSJM-A(1)]
1000
900
800
700
600
500
400
300
200
10 20 30 40 50 60 70 80 90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
1000
900
800
700
600
500
400
300
200
10 20 30 40 50 60 70 80 90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
1000
900
800
700
600
500
400
300
200
10 20 30 40 50 60 70 80 90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
1000
900
800
700
600
500
400
300
200
10 20 30 40 50 60 70 80 90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
1000
900
800
700
600
500
400
300
200
10 20 30 40 50 60 70 80 90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
1000
900
800
700
600
500
400
300
200
10 20 30 40 50 60 70 80 90 100 110
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
[3280]
[2952]
[2624]
[2296]
[1968]
[1640]
[1312]
[984]
[656]
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
Aggregate length of all pipes(m [ft])
Pipe length between outdoor unit and BC controller (m [ft])
0
10
20
30
40
50
60
70
0 5 10 15
Piping length between the main
BC controller and indoor units (m[ft])
Vertical separation between the main BC controller and indoor units (m[ft])
The height difference and the pipe length between BC controller and indoor units
[32]
[16] [32] [49]
[64]
[98]
[131]
[164]
[196]
[229]