Installation manual
[ II Restrictions ]
- 18 -
HWE10050 GB
(2) High COP combinations
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
Outdoor units Composing units Maximum total capacity
of connectable indoor
units
Maximum number
of connectable in-
door units
Types of connectable
indoor units
EP200 YJM-A - - 100 - 300 20 P15 - P250 models
R410A series indoor
units
EP250 YJM-A - - 125 - 375 25
EP300 YJM-A - - 150 - 450 30
EP350 YJM-A - - 175 - 525 35
EP400 YSJM-A EP200YJM-A EP200YJM-A 200 - 600 40
EP450 YSJM-A EP250YJM-A EP200YJM-A 225 - 675 45
EP500 YSJM-A EP300YJM-A EP200YJM-A 250 - 750 50
YSJM-A1 EP250YJM-A EP250YJM-A 250 - 750
EP550 YSJM-A EP300YJM-A EP250YJM-A 275 - 825
EP600 YSJM-A EP300YJM-A EP300YJM-A 300 - 900
YSJM-A1 EP350YJM-A EP250YJM-A 300 - 900
EP650 YSJM-A EP350YJM-A EP300YJM-A 325 - 975
EP700 YSJM-A EP350YJM-A EP350YJM-A 350 - 1050