Installation manual

[ II Restrictions ]
- 17 -
HWE10050 GB
II Restrictions
[1] System configuration
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
(1) Standard combinations
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the
indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of
units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
Outdoor units Composing units Maximum total capacity
of connectable indoor
units
Maximum number
of connectable in-
door units
Types of connectable
indoor units
P200 YJM-A - - 100 - 300 20 P15 - P250 models
R410A series indoor
units
P250 YJM-A - - 125 - 375 25
P300 YJM-A - - 150 - 450 30
P350 YJM-A - - 175 - 525 35
P400 YJM-A - - 200 - 600 40
YSJM-A1 P200YJM-A P200YJM-A 200 - 600
P450 YJM-A - - 225 - 675 45
YSJM-A1 P250YJM-A P200YJM-A 225 - 675
P500 YSJM-A P250YJM-A P250YJM-A 250 - 750 50
YSJM-A1 P300YJM-A P200YJM-A 250 - 750
P550 YSJM-A P300YJM-A P250YJM-A 275 - 825
P600 YSJM-A P300YJM-A P300YJM-A 300 - 900
YSJM-A1 P350YJM-A P250YJM-A 300 - 900
P650 YSJM-A P350YJM-A P300YJM-A 325 - 975
P700 YSJM-A P400YJM-A P300YJM-A 350 - 1050
YSJM-A1 P350YJM-A P350YJM-A 350 - 1050
P750 YSJM-A P400YJM-A P350YJM-A 375 - 1125
P800 YSJM-A P400YJM-A P400YJM-A 400 - 1200
YSJM-A1 P450YJM-A P350YJM-A 400 - 1200
P850 YSJM-A P450YJM-A P400YJM-A 425 - 1275
P900 YSJM-A P450YJM-A P450YJM-A 450 - 1350