Installation manual
[ VIII Test Run Mode ]
- 222 -
HWE10050 GB
Operation
Outdoor unit model
PURY-EP700YSJM-A
PURY-EP350YJM-A PURY-EP350YJM-A
Model name of BC controller CMB-P1016V-HA1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/ -
[68°F/ -]
Outdoor
7°C/ 6°C
[45°F/ 43°F]
Indoor unit
No. of connected units
Unit
7
No. of units in operation 7
Model
-
100/100/100/100/100/100/100
Fan speed Hi
Piping
Main pipe
m
[ft]
5[17]
Branch pipe 10 [33]
Total pipe length 75 [247]
Amount of refrigerant
kg
[lbs-oz]
40.6 [90]
Outdoor
unit
Electric current A 23.2
Voltage V 400
Compressor frequency Hz 101 101
LEV open-
ing
Indoor unit
Pulse
332/332/332/332/332/332/332
BC controller (LEV1/LEV3) 110/1220
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.88/ 0.65 2.88/ 0.65
[418/ 94] [418/ 94]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.84/ 2.52
[412/ 365]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
80 [176] 80 [176]
Heat exchanger inlet
(TH6)
1 [34] 1 [34]
Accumulator inlet (TH5) -1 [30] -1 [30]
Accumulator outlet -2 [28] -2 [28]
Compressor inlet -2 [28] -2 [28]
Compressor shell bottom 41 [106] 41 [106]
Indoor unit
LEV inlet 38 [100]
Heat exchanger gas pipe
(TH3)
70 [158]