Installation manual

[ VIII Test Run Mode ]
- 214 -
HWE10050 GB
(2) Heating only operation
Operation
Outdoor unit model
PURY-EP400YSJM-A
PURY-EP200YJM-A PURY-EP200YJM-A
Model name of BC controller CMB-P108V-GA1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/ -
[68°F/ -]
Outdoor
7°C/ 6°C
[45°F/ 43°F]
Indoor unit
No. of connected units
Unit
4
No. of units in operation 4
Model
-
100/100/100/100
Fan speed Hi
Piping
Main pipe
m
[ft]
5[17]
Branch pipe 10 [33]
Total pipe length 45 [148]
Amount of refrigerant
kg
[lbs-oz]
30.1 [67]
Outdoor
unit
Electric current A 11.9
Voltage V 400
Compressor frequency Hz 53 53
LEV open-
ing
Indoor unit
Pulse
332/332/332/332
BC controller (LEV1/LEV3) 110/800
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.64/ 0.69 2.64/ 0.69
[383/ 100] [383/ 100]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.61/ 2.29
[379/ 332]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
73 [163] 73 [163]
Heat exchanger inlet
(TH6)
1 [34] 1 [34]
Accumulator inlet (TH5) 0 [32] 0 [32]
Accumulator outlet -1 [30] -1 [30]
Compressor inlet -1 [30] -1 [30]
Compressor shell bottom 42 [108] 42 [108]
Indoor unit
LEV inlet 37 [99]
Heat exchanger gas pipe
(TH3)
70 [158]