Installation manual
[ VIII Test Run Mode ]
- 212 -
HWE10050 GB
Operation
Outdoor unit model
PURY-EP650YSJM-A
PURY-EP350YJM-A PURY-EP300YJM-A
Model name of BC controller CMB-P108V-GA1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C
[81°F/ 66°F]
Outdoor
35°C/ -
[95°F/ -]
Indoor unit
No. of connected units
Unit
6
No. of units in operation 6
Model
-
100/100/100/100/125/125
Fan speed Hi
Piping
Main pipe
m
[ft]
5[17]
Branch pipe 10 [33]
Total pipe length 65 [214]
Amount of refrigerant
kg
[lbs-oz]
40.0 [89]
Outdoor
unit
Electric current A 20.0
Voltage V 400
Compressor frequency Hz 95 74
LEV open-
ing
Indoor unit
Pulse
325/325/325/325/387/387
BC controller (LEV1/LEV3) 2000/250
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
3.08/ 0.83 3.08/ 0.83
[447/ 120] [447/ 120]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.83/ 2.83
[410/ 410]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
89 [192] 89 [192]
Heat exchanger outlet
(TH3)
40 [104] 40 [104]
Accumulator inlet (TH5) 8 [46] 8 [46]
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 19 [66] 19 [66]
Compressor shell bottom 42 [108] 42 [108]
Indoor unit
LEV inlet 19 [66]
Heat exchanger liquid
pipe (TH2)
6[43]