Installation manual
[ VIII Test Run Mode ]
- 203 -
HWE10050 GB
(2) Heating only operation
Operation
Outdoor unit model
PURY-EP200YJM-A PURY-EP250YJM-A
Model name of BC controller CMB-P104V-G1 CMB-P104V-G1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/ - 20°C/ -
[68°F/ -] [68°F/ -]
Outdoor
7°C/ 6°C 7°C/ 6°C
[45°F/ 43°F] [45°F/ 43°F]
Indoor unit
No. of connected units
Unit
22
No. of units in operation 2 2
Model
-
100/100 125/125
Fan speed Hi Hi
Piping
Main pipe
m
[ft]
5 [17] 5 [17]
Branch pipe 10 [33] 10 [33]
Total pipe length 25 [82] 25 [82]
Amount of refrigerant
kg
[lbs-oz]
16.3 [36] 19.8 [44]
Outdoor
unit
Electric current A 5.8 7.5
Voltage V 400 400
Compressor frequency Hz 53 71
LEV open-
ing
Indoor unit
Pulse
332/332 406/406
BC controller (LEV1/LEV3) 110/520 110/590
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.64/ 0.69 2.90/ 0.67
[383/ 100] [421/ 97]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.61/ 2.29 2.87/ 2.55
[379/ 332] [416/ 370]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
73 [163] 80 [176]
Heat exchanger inlet
(TH6)
1 [34] 1 [34]
Accumulator inlet (TH5) 0 [32] -1 [30]
Accumulator outlet -1 [30] -2 [28]
Compressor inlet -1 [30] -2 [28]
Compressor shell bottom 42 [108] 41 [106]
Indoor unit
LEV inlet 37 [99] 38 [100]
Heat exchanger gas pipe
(TH3)
70 [158] 70 [158]