Installation manual

[ VIII Test Run Mode ]
- 201 -
HWE10050 GB
3. Single unit (High-COP)
(1) Cooling only operation
Operation
Outdoor unit model
PURY-EP200YJM-A PURY-EP250YJM-A
Model name of BC controller CMB-P104V-G1 CMB-P104V-G1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C 27°C/ 19°C
[81°F/ 66°F] [81°F/ 66°F]
Outdoor
35°C/ - 35°C/ -
[95°F/ -] [95°F/ -]
Indoor unit
No. of connected units
Unit
22
No. of units in operation 2 2
Model
-
100/100 125/125
Fan speed Hi Hi
Piping
Main pipe
m
[ft]
5 [17] 5 [17]
Branch pipe 10 [33] 10 [33]
Total pipe length 25 [82] 25 [82]
Amount of refrigerant
kg
[lbs-oz]
16.3 [36] 19.8 [44]
Outdoor
unit
Electric current A 5.3 7.1
Voltage V 400 400
Compressor frequency Hz 52 65
LEV open-
ing
Indoor unit
Pulse
325/325 387/387
BC controller (LEV1/LEV3) 2000/160 2000/170
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.66/ 0.80 2.60/ 0.78
[385/ 116] [377/ 113]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.51/ 2.51 2.45/ 2.45
[363/ 363] [355/ 355]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
83 [181] 77 [171]
Heat exchanger outlet
(TH3)
32 [90] 31 [88]
Accumulator inlet (TH5) 8 [46] 8 [46]
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 19 [66] 19 [66]
Compressor shell bottom 47 [117] 40 [104]
Indoor unit
LEV inlet 19 [66] 19 [66]
Heat exchanger liquid
pipe (TH2)
6 [43] 6 [43]