Installation manual

[ VIII Test Run Mode ]
- 197 -
HWE10050 GB
Operation
Outdoor unit model
PURY-P800YSJM-A
PURY-P400YJM-A PURY-P400YJM-A
Model name of BC controller CMB-P1016V-HA1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
20°C/ -
[68°F/ -]
Outdoor
7°C/ 6°C
[45°F/ 43°F]
Indoor unit
No. of connected units
Unit
8
No. of units in operation 8
Model
-
100/100/100/100/100/100/100/100
Fan speed Hi
Piping
Main pipe
m
[ft]
5[17]
Branch pipe 10 [33]
Total pipe length 85 [279]
Amount of refrigerant
kg
[lbs-oz]
43.2 [96]
Outdoor
unit
Electric current A 27.3
Voltage V 400
Compressor frequency Hz 102 102
LEV open-
ing
Indoor unit
Pulse
332/332/332/332/332/332/332/332
BC controller (LEV1/LEV3) 110/1360
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.68/ 0.56 2.68/ 0.56
[389/ 81] [389/ 81]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.64/ 2.32
[383/ 336]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
82 [180] 82 [180]
Heat exchanger inlet
(TH6)
1 [34] 1 [34]
Accumulator inlet (TH5) -4 [25] -4 [25]
Accumulator outlet -4 [25] -4 [25]
Compressor inlet -4 [25] -4 [25]
Compressor shell bottom 40 [104] 40 [104]
Indoor unit
LEV inlet 37 [99]
Heat exchanger gas pipe
(TH3)
70 [158]