Installation manual

[ VIII Test Run Mode ]
- 185 -
HWE10050 GB
Operation
Outdoor unit model
PURY-P900YSJM-A
PURY-P450YJM-A PURY-P450YJM-A
Model name of BC controller CMB-P1016V-HA1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C
[81°F/ 66°F]
Outdoor
35°C/ -
[95°F/ -]
Indoor unit
No. of connected units
Unit
9
No. of units in operation 9
Model
-
100/100/100/100/100/100/100/100/100
Fan speed Hi
Piping
Main pipe
m
[ft]
5[17]
Branch pipe 10 [33]
Total pipe length 95 [312]
Amount of refrigerant
kg
[lbs-oz]
45.8 [101]
Outdoor
unit
Electric current A 31.7
Voltage V 400
Compressor frequency Hz 111 111
LEV open-
ing
Indoor unit
Pulse
325/325/325/325/325/325/325/325/325
BC controller (LEV1/LEV3) 2000/300
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
3.15/ 0.85 3.15/ 0.85
[457/ 123] [457/ 123]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.70/ 2.70
[392/ 392]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
90 [194] 90 [194]
Heat exchanger outlet
(TH3)
40 [104] 40 [104]
Accumulator inlet (TH5) 8 [46] 8 [46]
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 19 [66] 19 [66]
Compressor shell bottom 40 [104] 40 [104]
Indoor unit
LEV inlet 17 [63]
Heat exchanger liquid
pipe (TH2)
4[39]