Installation manual

[ VIII Test Run Mode ]
- 181 -
HWE10050 GB
Operation
Outdoor unit model
PURY-P750YSJM-A
PURY-P400YJM-A PURY-P350YJM-A
Model name of BC controller CMB-P1016V-HA1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C
[81°F/ 66°F]
Outdoor
35°C/ -
[95°F/ -]
Indoor unit
No. of connected units
Unit
7
No. of units in operation 7
Model
-
100/100/100/100/100/125/125
Fan speed Hi
Piping
Main pipe
m
[ft]
5[17]
Branch pipe 10 [33]
Total pipe length 75 [247]
Amount of refrigerant
kg
[lbs-oz]
42.6 [94]
Outdoor
unit
Electric current A 27.8
Voltage V 400
Compressor frequency Hz 97 95
LEV open-
ing
Indoor unit
Pulse
325/325/325/325/325/387/387
BC controller (LEV1/LEV3) 2000/270
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
3.10/ 0.84 3.10/ 0.84
[450/ 122] [450/ 122]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.74/ 2.74
[397/ 397]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
91 [196] 91 [196]
Heat exchanger outlet
(TH3)
41 [106] 41 [106]
Accumulator inlet (TH5) 8 [46] 8 [46]
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 19 [66] 19 [66]
Compressor shell bottom 41 [106] 41 [106]
Indoor unit
LEV inlet 18 [64]
Heat exchanger liquid
pipe (TH2)
5[41]