Installation manual

[ VIII Test Run Mode ]
- 176 -
HWE10050 GB
Operation
Outdoor unit model
PURY-P600YSJM-A
PURY-P300YJM-A PURY-P300YJM-A
Model name of BC controller CMB-P108V-GA1
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
27°C/ 19°C
[81°F/ 66°F]
Outdoor
35°C/ -
[95°F/ -]
Indoor unit
No. of connected units
Unit
6
No. of units in operation 6
Model
-
100/100/100/100/100/100
Fan speed Hi
Piping
Main pipe
m
[ft]
5[17]
Branch pipe 10 [33]
Total pipe length 65 [214]
Amount of refrigerant
kg
[lbs-oz]
34.4 [76]
Outdoor
unit
Electric current A 20.6
Voltage V 400
Compressor frequency Hz 74 74
LEV open-
ing
Indoor unit
Pulse
325/325/325/325/325/325
BC controller (LEV1/LEV3) 2000/240
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
3.12/ 0.86 3.12/ 0.86
[453/ 125] [453/ 125]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.93/ 2.93
[425/ 425]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
86 [187] 86 [187]
Heat exchanger outlet
(TH3)
41 [106] 41 [106]
Accumulator inlet (TH5) 8 [46] 8 [46]
Accumulator outlet 8 [46] 8 [46]
Compressor inlet 19 [66] 19 [66]
Compressor shell bottom 42 [108] 42 [108]
Indoor unit
LEV inlet 19 [66]
Heat exchanger liquid
pipe (TH2)
6[43]